Discrepancy time expired
ABB · AC500-S Safety Controller
Was bedeutet 3 ?
The configured discrepancy time for redundant inputs has elapsed, meaning that the states of redundant channels did not synchronize within the expected timeframe. This indicates a fault in the sensors, wiring, or configuration, preventing valid safety signal evaluation.
Häufige Ursachen
- One of the redundant input sensors (e.g., safety gate switch S1 vs S2) has a significantly slower response time or actuation delay than the other.
- Intermittent signal loss or delay on one of the redundant input channels due to wiring issues (e.g., a loose connection at terminal X2.5 delaying signal transmission).
- The configured discrepancy time (e.g., Parameter S2-01) in the safety controller is set too short for the normal operational differences between the redundant sensors or the application's physical response.
- A physical obstruction or mechanical issue preventing one sensor from actuating or de-actuating in sync with its redundant counterpart.
- One of the redundant sensors is intermittently sticking or failing to change state reliably, leading to timing mismatches.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Actuate and de-actuate the safety function (e.g., opening and closing a guard door) while monitoring the status of both redundant inputs in the PLC's diagnostic view, observing their transition times.
- 2
Using an oscilloscope or logic analyzer, measure the actual signal transition times of both redundant inputs directly at the I/O module terminals to identify delays.
- 3
Verify the configured discrepancy time (e.g., Parameter S2-01) in the safety controller's programming matches the expected operational delays and adjust it if necessary (with careful safety assessment).
- 4
Perform a continuity test on the wiring for both redundant channels to rule out intermittent open circuits or high resistance that could cause signal delays.
- 5
If one sensor consistently responds slower or fails to transition, isolate and test that specific sensor for mechanical or electrical faults; replace if confirmed faulty.