Access Test Failed / Internal Error (SM560-S)
ABB · AC500-S Safety Controller
Was bedeutet E2-17 ?
An access test to the Safety PLC has failed, or an internal error has occurred within the Safety PLC. This can be due to incorrect address settings or a hardware malfunction, preventing proper access or operation.
Häufige Ursachen
- Incorrect IP address or network settings configured for the SM560-S Safety PLC, preventing communication from the engineering workstation.
- Hardware malfunction within the Ethernet port or communication processor of the SM560-S PLC, preventing it from responding to access requests.
- Damaged or faulty Ethernet cable (e.g., Cat5e or Cat6) connecting the engineering workstation to the Safety PLC, causing intermittent or no communication.
- Firmware bug or internal operating system error in the SM560-S PLC preventing it from correctly handling communication requests or diagnostic tests.
- Network firewall settings on the engineering workstation or an intermediate network device blocking communication ports (e.g., Port 1200) required for PLC access.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Verify the IP address and subnet mask settings of the SM560-S Safety PLC via its display or a direct connection, ensuring they match the engineering workstation's network configuration.
- 2
2. Replace the Ethernet cable connecting the engineering workstation to the Safety PLC's programming port with a known good, certified Cat5e or Cat6 patch cable.
- 3
3. Ping the Safety PLC's IP address from the engineering workstation's command prompt to verify basic network connectivity (e.g., 'ping 192.168.1.10').
- 4
4. Power cycle the SM560-S Safety PLC and attempt to access it again via the engineering software immediately after it restarts.
- 5
5. If direct access fails, attempt to connect via a different communication path (e.g., serial port, if available) to check basic functionality.
- 6
6. If all other steps fail, consider replacing the SM560-S Safety PLC CPU module with a known good spare.