Übersetzen...
16153

PROFIsafe Watchdog Timed Out

ABB · AC500

Was bedeutet 16153 ?

The PROFIsafe watchdog timer has expired, meaning the safety I/O module did not receive a valid PROFIsafe telegram within the expected timeframe. This indicates a communication interruption or delay that prevents the safety system from functioning correctly, leading to a safe state.

Häufige Ursachen

  • Severe communication interruption or loss of connection between the safety CPU and the safety I/O module.
  • The PROFIsafe watchdog timer parameter (F_WD_Time) in the configuration is set too short for the actual network update rate.
  • High network load or latency causing delays in PROFIsafe telegrams, exceeding the watchdog period.
  • Intermittent fault in the PROFIBUS/PROFINET infrastructure (e.g., faulty switch port, damaged coupler).
  • Internal communication processor failure within the safety I/O module.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Check the network status LEDs on both the safety CPU and the safety I/O module for communication errors or link failures.

  2. 2

    2. Verify the physical PROFIBUS/PROFINET connection and check for loose cables or damaged connectors.

  3. 3

    3. Review and potentially increase the F_WD_Time parameter in the safety configuration to allow for network variations.

  4. 4

    4. Monitor the network traffic and bus cycle time using a network analyzer to identify excessive delays or telegram loss.

  5. 5

    5. If all communication path components are verified, perform a firmware update on the safety I/O module or replace the module.

Alle Codes in diesem Handbuch durchsuchen (54)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes