Übersetzen...
8110

Analog Input Below Minimum Function

ABB · ACS560 Standard Control Program Firmware

Was bedeutet 8110 ?

An analogue input signal has fallen below its set minimum limit, which can cause the drive to react by either tripping or setting the speed to a predefined value. This warning indicates a potential loss of critical feedback or reference signal, which could lead to unsafe or unintended operation if not addressed.

Häufige Ursachen

  • Broken wire or loose connection in the analog input signal circuit (e.g., 4-20mA loop, 0-10VDC source).
  • Faulty external sensor or transducer providing the analog input (e.g., pressure sensor outputting 0mA).
  • Incorrect scaling of the analog input parameter (e.g., P09-01, P09-02 for minimum/maximum limits).
  • External power supply for the analog sensor failed (e.g., 24VDC supply for current loop).
  • Incorrect configuration of the analog input type (e.g., P09-00 set for current input when voltage input is used).

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the voltage or current at the drive's analog input terminals (e.g., AI1, AI2) using a multimeter.

  2. 2

    Verify the external sensor or transducer connected to the analog input is powered and producing its expected output signal.

  3. 3

    Check drive parameters P09-00 (Analog Input 1 Type), P09-01 (Analog Input 1 Minimum), and P09-02 (Analog Input 1 Maximum) for correct configuration.

  4. 4

    Inspect the wiring from the analog sensor to the drive's analog input terminals for continuity and secure connections.

  5. 5

    Temporarily bypass the external sensor and apply a known, stable analog signal (e.g., 5VDC from a power supply) to the drive's input to test the drive's response.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes