Hardware Reconfiguration Request
ABB · ACS560 Standard Control Program Firmware
Was bedeutet FF38 ?
The inverter type (e.g., sr0025_3) has been changed, typically at the factory or during drive implementation. This fault indicates that the new configuration needs to be validated before the drive can operate correctly, requiring a specific power-off sequence.
Häufige Ursachen
- Drive control board or power module replaced with a different model or firmware version.
- Firmware update initiated but not fully validated or a mismatch detected.
- Parameter backup/restore operation performed with a file from a different drive model or configuration.
- Corruption of internal drive configuration memory requiring reinitialization.
- Installation of an incompatible option card (e.g., I/O extension, communication module).
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Confirm the model and firmware version of the installed control board and power module match the original specification.
- 2
Perform a factory reset (e.g., P99-01 = 1) and then re-enter or reload parameters from a known good backup file.
- 3
Verify all installed option cards (e.g., fieldbus module, I/O extension) are compatible with the drive model and firmware.
- 4
Attempt to re-upload the correct firmware using the manufacturer's commissioning tool, ensuring checksum validation passes.
- 5
If available, try swapping the control board with a known good, compatible spare, then attempt to power cycle the drive.