6684

EFB load fault

ABB · ACS580

Was bedeutet 6684 ?

The embedded fieldbus (EFB) protocol firmware could not be loaded, or there is a version mismatch between the EFB protocol firmware and the main drive firmware. This critical error prevents the EFB from functioning, thus disabling fieldbus communication.

Häufige Ursachen

  • EFB option module firmware is corrupted or incomplete due to an interrupted update or memory error.
  • Main drive firmware version is incompatible with the installed EFB protocol firmware version (e.g., main firmware v3.x and EFB firmware v2.x).
  • EFB option module hardware fault preventing proper firmware loading during drive startup.
  • Incorrect EFB protocol package selected for download or stored on the drive's memory during a firmware update procedure.
  • Insufficient memory available on the EFB module or main control board to load the protocol firmware.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Record current drive and EFB firmware versions (e.g., from P0-01 and P0-02) for reference.

  2. 2

    Download the compatible EFB protocol firmware package for the drive's main firmware version from the manufacturer's website.

  3. 3

    Attempt to re-flash the EFB protocol firmware using the drive's flashing utility (e.g., via Drive Composer through USB or Ethernet).

  4. 4

    Power down the drive, remove the EFB option module, inspect its connectors for damage, and re-insert it firmly into its slot.

  5. 5

    If the fault persists after re-flashing and re-seating, replace the EFB option module.