DC Bus Limit

ABB · ACS800 Standard Firmware

Was bedeutet 3211 ?

The drive is limiting torque due to an intermediate circuit DC voltage that is either too high or too low. This is an informative alarm (programmable Fault Function 30.23, bit 1: DC_VOLT_LIM_IND) indicating the drive is actively compensating to protect internal components from over or undervoltage conditions.

Häufige Ursachen

  • DC bus voltage exceeding the maximum allowable limit.
  • Overly aggressive deceleration ramp causing regenerative braking energy overload.
  • External braking resistor failure or undersized for the application.
  • Control parameters (e.g., P2-20) set too high for the system's regenerative capacity.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check Fault Function parameter 30.23 (LIMIT WARNING) to ensure it is correctly configured for DC bus voltage supervision.