Übersetzen...
3220
DC UNDERVOLT
ABB · ACS800 Standard Firmware
Was bedeutet 3220 ?
The intermediate circuit DC voltage is insufficient, which can be caused by a missing supply voltage phase, a blown input fuse, or an internal fault within the rectifier bridge. The DC undervoltage trip limit is 0.6 × 1.35 × U1min, corresponding to 307 VDC for 400 V and 500 V units, and 425 VDC for 690 V units. This fault is associated with bit 2 of Fault Word 2 (3.06 FW 2).
Häufige Ursachen
- DC bus voltage is too low to operate the drive.
- Low input AC voltage.
- Insufficient power supply capacity.
- Fault in the DC bus rectifier or pre-charge circuit.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure and verify the incoming three-phase main supply voltage at the drive input terminals (e.g., L1, L2, L3).
- 2
Inspect all main input fuses for continuity using a multimeter and replace any found to be blown.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: ABB ACS800 Standard Firmware