Übersetzen...
7301
Encoder Error
ABB · ACS800 Standard Firmware
Was bedeutet 7301 ?
A communication fault exists between the pulse encoder and its interface module, or between the interface module and the drive itself. This prevents accurate speed and position feedback, potentially causing control instability or incorrect motor operation.
Häufige Ursachen
- Encoder internal fault or failure.
- Loss of communication signal from the encoder.
- Encoder power supply issue (check P0-09).
- Encoder resolution mismatch or incorrect model selected.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect the pulse encoder unit and its wiring for damage, loose connections, or shielding issues.
- 2
Inspect the pulse encoder interface module and its wiring for damage, loose connections, or proper installation.
- 3
Check parameter group 50 (ENCODER MODULE) settings to ensure correct encoder configuration.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: ABB ACS800 Standard Firmware