Übersetzen...
8110

Analog Input Below Minimum

ABB · ACS800 Standard Firmware

Was bedeutet 8110 ?

An analog input signal (e.g., 0-10V, 4-20mA) has fallen below its configured minimum limit, which must be set to 0.5V (1 mA) or above in parameter group 13. Depending on parameter 30.01 (AI<MIN FUNCTION), the drive may trip, set a constant speed (12.16), or freeze at the last operating speed.

Häufige Ursachen

  • Analog input signal (e.g., AI1, AI2) is below its configured minimum threshold (P7-01, P7-02).
  • Sensor failure providing a reading outside expected operational range.
  • Incorrect calibration of the analog input signal.
  • Wiring issue or short circuit on the analog input line.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify parameter 30.01 (AI<MIN FUNCTION) is set correctly for the desired drive reaction upon signal loss.

  2. 2

    Measure the analog input signal at its respective terminals (e.g., AI1, AI2) to confirm it is above the set minimum limit.

  3. 3

    Review parameter settings in group 13 (ANALOGUE INPUTS) to confirm the minimum limit is configured correctly, typically 0.5V (1mA) or above.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes