FF89
MOD CHOKE T
ABB · ACS800 Standard Firmware
Was bedeutet FF89 ?
An overtemperature condition has been detected in the choke of a liquid-cooled R8i inverter module. This indicates that the choke's temperature has surpassed its safe operating threshold.
Häufige Ursachen
- Over-temperature condition detected on a choke or filtering component.
- Excessive current flowing through the choke.
- Choke saturation or damage.
- Poor ventilation around the choke.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect the inverter cooling fan for proper operation, obstructions, or unusual noises.
- 2
Measure the ambient temperature around the inverter module and verify it is within the specified operating range.
- 3
Check the liquid cooling system for adequate flow, pressure, and coolant level to ensure effective heat removal.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: ABB ACS800 Standard Firmware