Übersetzen...
10030

PDO data is not present (Cn to Mn) (_ecPDO_DATA_MISSING_CN_TO_MN)

ABB · ACS850 Standard Program Firmware

Was bedeutet 10030 ?

This fault indicates a loss of Process Data Object (PDO) communication between a remote axis (Client Node, CN) and the manager (Master Node, MN), specifically when at least two consecutive PDO packets are not received. For a NextMove e100, it means a drive has disappeared from the network. Unresolved, this can lead to loss of control over the remote axis and system instability.

Häufige Ursachen

  • Intermittent or broken EtherCAT communication cable (e.g., CAT5e/CAT6) between the Master Node and Client Node.
  • Incorrect EtherCAT network configuration (e.g., Master Node not mapping expected PDOs from Client Node).
  • Client Node (drive) power cycling or temporary power loss causing it to drop off the network.
  • Excessive electromagnetic interference (EMI) on the EtherCAT network cable disrupting data packets.
  • Master Node's cycle time too short or Client Node's response time too slow, leading to missed PDOs.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Inspect the EtherCAT cable between the Master Node and Client Node for physical damage, ensuring secure connections at both RJ45 ports.

  2. 2

    2. Verify the EtherCAT cable shield is properly terminated at the master and slave devices to mitigate EMI.

  3. 3

    3. Check the Master Node's configuration file for correct PDO mapping and update rates for the Client Node.

  4. 4

    4. Monitor the network status LEDs on both the Master and Client Node (e.g., EtherCAT Link/Activity LEDs) for link integrity.

  5. 5

    5. Review the Master Node's diagnostic log for specific communication errors related to the Client Node ID.

  6. 6

    6. Temporarily reduce the EtherCAT Master's cycle time or increase the watchdog timeout period (if configurable) to test for timing issues.

Alle Codes in diesem Handbuch durchsuchen (57)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: ABB ACS850 Standard Program Firmware