Auxiliary fan not running
ABB · ACS880
Was bedeutet 5081 ?
An auxiliary fan fault has been detected; the auxiliary fan is not running. This compromises secondary cooling. The drive trips after a 2-minute suppression period during power-up, during which it only issues a warning. Continued operation without auxiliary cooling can lead to overheating.
Häufige Ursachen
- Auxiliary cooling fan motor has failed mechanically (e.g., seized bearings) or electrically (e.g., open winding).
- Control circuit for the auxiliary fan on the drive's PCB has failed, preventing power delivery to the fan.
- Wiring connection to the auxiliary fan unit is loose, broken, or has high resistance.
- Debris or foreign material has entered the auxiliary fan housing, physically obstructing its rotation.
- Auxiliary fan power supply (often DC) is absent or below the required operating voltage.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Power down and visually inspect the auxiliary fan for obstructions, then gently attempt to manually rotate the blades to check for binding.
- 2
2. With power on (and observing safety precautions), confirm that the auxiliary fan is not spinning and there are no abnormal noises.
- 3
3. Measure the DC voltage supplied to the auxiliary fan connector (e.g., 24VDC) at the drive's control board output.
- 4
4. Test the continuity of the wiring harness connecting the auxiliary fan to the drive's control board.
- 5
5. Replace the auxiliary fan unit with an equivalent manufacturer-specified part to ensure correct functionality.