7181

Brake resistor

ABB · ACS880

Was bedeutet 7181 ?

The drive detects an issue with the brake resistor, indicating it might be disconnected, physically damaged, or improperly sized. This prevents proper dissipation of regenerative energy, potentially leading to DC bus overvoltage and drive trips during deceleration.

Häufige Ursachen

  • Brake resistor (BR) disconnected from the drive's BR+ and BR- terminals.
  • Open circuit detected in the brake resistor element due to internal damage or wire breakage.
  • Incorrect brake resistor value (resistance or power rating) specified in drive parameter P4-01 or P4-02.
  • Loose or corroded connections at the brake resistor terminals.
  • Faulty internal brake chopper circuit not accurately sensing the resistor.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Power off and lock out the drive. Verify physical connection of the brake resistor to the drive's BR+ and BR- terminals.

  2. 2

    Measure the resistance of the brake resistor across its terminals using a multimeter; compare to the nameplate value.

  3. 3

    Confirm drive parameter P4-01 (Brake Resistor Resistance) matches the measured resistance value within tolerance.

  4. 4

    Inspect brake resistor wiring for breaks, damage, or loose connections.

  5. 5

    Check the drive's fault log for preceding or related brake chopper faults (e.g., 7191 BC short circuit).