A887

On-time 2

ABB · ACS880

Was bedeutet A887 ?

Warning generated by on-time timer 2, indicating that a predefined operational time limit has been reached or exceeded. This often serves as a maintenance reminder or an alert for extended operation. Failure to address could lead to component wear or overdue service.

Häufige Ursachen

  • On-time timer 2 (Parameter P4-04) has exceeded its programmed limit (P4-04.01 On-time 2 Limit), signaling a second independent maintenance or operational threshold.
  • The component or process linked to this timer has reached its defined operational period without scheduled service.
  • The threshold for On-time Timer 2 (P4-04.01) was misconfigured or is no longer appropriate for current operating conditions.
  • Previous maintenance related to On-time Timer 2 was performed, but the timer was not correctly reset.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Identify the specific equipment or process that On-time Timer 2 is configured to monitor by reviewing system documentation.

  2. 2

    Note the current accumulated time value displayed in parameter P4-04.00 (Current On-time 2).

  3. 3

    Perform the required preventative maintenance (e.g., gearbox oil change, motor fan inspection) corresponding to the timer's purpose.

  4. 4

    Reset On-time Timer 2 to zero by setting parameter P4-04.02 (Reset Timer 2) to '1' (Execute) after the maintenance is completed.

  5. 5

    Update the limit in parameter P4-04.01 (On-time 2 Limit) if the operational interval needs to be extended or reduced.