AE02

Earth leakage

ABB · ACS880

Was bedeutet AE02 ?

The supply unit generates a warning when an earth fault or current unbalance is detected. This indicates a potential insulation issue within the supply unit's power circuit or its input cabling, requiring attention to prevent a full fault trip or damage.

Häufige Ursachen

  • Insulation degradation or minor leakage in the input power cables (L1, L2, L3) supplying the drive's supply unit.
  • Moisture or conductive dust ingress within the supply unit itself, causing current to leak to ground.
  • Faulty input EMC filter components (e.g., Y-capacitors) developing a leakage path to ground.
  • Improper grounding of the supply unit or upstream power distribution components, leading to an unbalanced current detection.
  • Damage to the input rectifier bridge or DC-bus capacitors within the supply unit, creating a leakage path.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Disconnect the input power cables (L1, L2, L3) from the supply unit. Perform an insulation resistance test (Megger, e.g., 500VDC) on these cables to ground (PE).

  2. 2

    2. Visually inspect the interior of the supply unit for signs of moisture, contamination, or carbon tracking, especially around the input terminals.

  3. 3

    3. Verify that the PE (ground) connection to the supply unit's terminal block is tight and makes good contact.

  4. 4

    4. If accessible and safe, measure the resistance of the input EMC filter components to ground for any unexpected low values.

  5. 5

    5. Power cycle the entire system after ensuring all connections are secure and the environment inside the cabinet is clean and dry.