4312

MOTOR 1 TEMP

ABB · ACS800

Was bedeutet 4312 ?

The measured temperature from motor sensor 1, connected to the ABB ACS800 drive, has exceeded the alarm limit set by parameter 35.02. This fault (3.16 AW 4 bit 1) indicates a detected overheating condition in the motor, requiring immediate attention to prevent winding damage or component failure.

Häufige Ursachen

  • Motor temperature exceeding the alarm limit defined by parameter 35.02 (MOTOR 1 TEMP ALARM).
  • Incorrect setting of parameter 35.02 (MOTOR 1 TEMP ALARM), potentially set too low for normal operating conditions.
  • Incorrect number of temperature sensors configured in the drive compared to the actual sensors installed.
  • Motor overload, inadequate motor cooling, or high ambient temperature contributing to excessive heat.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Allow the motor to cool down. Identify and address the source of excessive motor heat, such as motor overload, insufficient cooling, or high ambient temperature.

  2. 2

    Verify the value set in parameter 35.02 (MOTOR 1 TEMP ALARM) is appropriate for the motor's thermal characteristics and the application.

  3. 3

    Ensure that the parameter reflecting the actual number of motor temperature sensors corresponds to the physical installation in the motor.

  4. 4

    Inspect the motor cooling fan for proper operation, clean cooling surfaces, and ensure clear airflow around the motor body.

  5. 5

    Check the motor's load and operating conditions to ensure they are within the motor's continuous rating, especially for long operating cycles.

Alle Codes in diesem Handbuch durchsuchen (33)