Übersetzen...
7112

BR OVERHEAT

ABB · ACS800

Was bedeutet 7112 ?

The brake resistor connected to the ABB ACS800 drive is experiencing an overload condition, leading to excessive temperature. This fault (3.17 FW 5 bit 3) can reduce braking effectiveness, potentially damage the resistor or associated components, and indicates that the braking duty cycle may be too demanding or improperly configured.

Häufige Ursachen

  • Brake resistor overload due to an excessive braking duty cycle for the application.
  • Incorrect parameter settings for the brake chopper or resistor overload protection in parameter group 27 BRAKE CHOPPER.
  • The braking cycle demands exceed the allowed limits for the installed brake resistor's thermal capacity.
  • Excessive AC supply voltage to the drive can affect regenerative braking behavior.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Stop the ABB ACS800 drive and allow the brake resistor to cool down to a safe operating temperature before resuming operation.

  2. 2

    Review and adjust parameter settings in group 27 BRAKE CHOPPER to ensure they match the installed brake resistor's specifications and the application's braking requirements.

  3. 3

    Evaluate the braking duty cycle of the application; ensure it meets the specifications of the brake resistor. Reduce braking demands or consider a larger resistor if consistently hitting limits.

  4. 4

    Measure the drive's AC supply voltage to confirm it is within specified limits and not excessively high, which can impact regenerative voltage levels.

  5. 5

    Inspect the brake resistor for any visible signs of physical damage, such as burnt areas, cracks, or discolored components.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes