Übersetzen...
0018

MEMORY MODULE USER PROGRAM INCOMPATIBLE WITH OS

Allen-Bradley · MicroLogix 1400 Programmable Controllers

Was bedeutet 0018 ?

The user program stored in the memory module is incompatible with the controller's current Operating System (OS). This is a non-user fault, indicating a fundamental mismatch that prevents the program from executing correctly.

Häufige Ursachen

  • Memory module contains a program compiled for a different or older OS version than currently installed.
  • Controller's OS is too old or too new for the program on the memory module.
  • Controller firmware was updated without ensuring program compatibility.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Upgrade the controller's OS using ControlFLASH to a version compatible with the memory module's user program.

  2. 2

    Obtain a new memory module containing a user program compatible with the current OS.

  3. 3

    Contact your local Rockwell Automation representative for more information about available operating systems compatible with your controller.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Allen-Bradley MicroLogix 1400 Programmable Controllers