F71

Net Loss

Allen-Bradley · PowerFlex 4 Adjustable Frequency

Was bedeutet F71 ?

This fault occurs when communication is lost with the network connected to the drive. This means the drive is no longer receiving commands or transmitting data via its communication interface.

Häufige Ursachen

  • Loss of communication with the main control network (e.g., Ethernet/IP, Profibus).
  • Faulty network cable or connector.
  • Network switch or router malfunction.
  • Incorrect network configuration (IP address, station address).

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the physical network cable connection to the drive's communication port (e.g., RS485/DSI terminals 8 and 1).

  2. 2

    Check the operational status of other devices on the communication network for faults or disconnections.

  3. 3

    Ensure all network communication parameters (e.g., A103 [CommData Rate], A104 [CommNode Addr], A107 [CommFormat]) are correctly configured and match the network settings.

Alle Codes in diesem Handbuch durchsuchen (24)