Übersetzen...
F2

Auxiliary Input

Allen-Bradley · PowerFlex 40 Adjustable Frequency

Was bedeutet F2 ?

This fault indicates an issue with a remote auxiliary input. This input is typically configured to trigger a fault condition when active or inactive, depending on the setup. This is an Auto-Reset/Run type fault configurable with parameters A092 and A093.

Häufige Ursachen

  • Auxiliary input wiring fault (e.g., open circuit, short circuit) causing an unexpected state at the drive's digital input (e.g., S3).
  • External control device (e.g., limit switch, E-stop button) connected to the auxiliary input has failed or is in an unexpected state (e.g., stuck open/closed).
  • Incorrect configuration of the auxiliary input's fault logic (e.g., P051 [Auxiliary Input Sel]) or state (e.g., Normally Open/Normally Closed) in the drive.
  • Loss of the 24VDC control power supply to the auxiliary input circuit or the external control device.
  • Interference or electrical noise on the auxiliary input signal line causing sporadic activation or deactivation.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the voltage across the auxiliary input terminals (e.g., S3, S4) relative to common (e.g., S1) on the drive to verify its active/inactive state.

  2. 2

    Check continuity of the auxiliary input wiring from the external device (e.g., limit switch) to the drive terminals.

  3. 3

    Verify drive parameter P051 [Auxiliary Input Sel] and its configured logic (e.g., N.O. or N.C. for the fault condition).

  4. 4

    Actuate the external control device manually and observe the input status on the drive's digital input monitoring screen.

  5. 5

    Confirm the 24VDC control power supply feeding the auxiliary input circuit is present and stable using a multimeter.

Alle Codes in diesem Handbuch durchsuchen (26)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Allen-Bradley PowerFlex 40 Adjustable Frequency