Übersetzen...
F4

UnderVoltage

Allen-Bradley · PowerFlex 4M Adjustable Frequency

Was bedeutet F4 ?

The drive has detected that the DC bus voltage has dropped below its predefined minimum operating threshold. This condition typically occurs due to low incoming AC line voltage, a momentary power interruption, or excessive voltage sag from the utility supply. Sustained undervoltage can prevent the drive from operating correctly, cause nuisance trips, or indicate a problem with the main power supply, potentially halting equipment operation.

Häufige Ursachen

  • Incoming AC line voltage consistently below the drive's minimum operating threshold (e.g., 340V for a 400V class drive).
  • Momentary power interruption (brownout) or significant voltage dip on the utility supply.
  • Overloaded input transformer or upstream circuit causing an excessive voltage drop under load.
  • Loose or corroded electrical connections at the drive's main power terminals (L1, L2, L3) increasing resistance.
  • Incorrectly set undervoltage trip level parameter (e.g., P0-03) too high for the nominal supply voltage.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure incoming AC line voltage at terminals L1, L2, L3 for phase-to-phase values under no-load and full-load conditions.

  2. 2

    Verify that the supply voltage consistently falls within the drive's specified input voltage range (e.g., 380-480VAC).

  3. 3

    Check all fuses and circuit breakers in the power path for proper continuity and correct rating.

  4. 4

    Inspect and retorque all main power connections at the drive (L1, L2, L3) and upstream power sources.

  5. 5

    Increase the undervoltage trip delay time (e.g., Parameter P1-30) if momentary sags are expected and tolerable for the application.

Alle Codes in diesem Handbuch durchsuchen (24)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Allen-Bradley PowerFlex 4M Adjustable Frequency