Übersetzen...
13
Ground Fault
Allen-Bradley · PowerFlex 700
Was bedeutet 13 ?
A current path to earth ground greater than 25% of the drive rating has been detected on the output. This indicates an insulation breakdown or short circuit between the motor phases or wiring and ground, which is a severe safety and equipment risk.
Häufige Ursachen
- Short circuit between motor phases and ground.
- Damaged motor winding insulation.
- Faulty motor power cable.
- Grounding issue within the drive or motor.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the motor for a grounded condition (e.g., measure insulation resistance from motor phases to ground).
- 2
Check the external wiring between the drive output terminals and the motor for a grounded condition.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Allen-Bradley PowerFlex 700