24

Decel Inhibit

Allen-Bradley · PowerFlex 700

Was bedeutet 24 ?

The drive is not following a commanded deceleration because it is attempting to limit bus voltage. This indicates the DC bus voltage is rising due to regenerative energy, potentially exceeding safe limits and causing the drive to inhibit deceleration.

Häufige Ursachen

  • External signal preventing deceleration (e.g., motor brake active).
  • Internal logic error during deceleration command.
  • Deceleration ramp time set too short for the load.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify input voltage is within the drive's specified limits.

  2. 2

    Verify system ground impedance follows proper grounding techniques.

  3. 3

    Disable bus regulation and/or add a dynamic brake resistor and/or extend the deceleration time parameter.

Alle Codes in diesem Handbuch durchsuchen (49)