Übersetzen...
41

Phase UV Short

Allen-Bradley · PowerFlex 700

Was bedeutet 41 ?

Excessive current has been detected between output terminals U and V. This indicates a short circuit condition between these two motor phases or their connecting wiring, leading to very high currents and potential drive damage.

Häufige Ursachen

  • Short circuit detected between Phase U and Phase V.
  • Damaged insulation between Phase U and Phase V motor windings.
  • Faulty motor power cable with U and V shorted.
  • Internal short circuit in the drive's output stage.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the motor and drive output terminal wiring for a shorted condition between U and V.

  2. 2

    Replace the drive if wiring and motor are verified good.

Alle Codes in diesem Handbuch durchsuchen (49)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes