Übersetzen...
4 pulses (arg n)

K-bus Data Error - Break Behind Bus Terminal n

Beckhoff · CX2100-0914 Embedded PC

Was bedeutet 4 pulses (arg n) ?

The K-bus ERR LED flashes 4 times, with 'n' pulses in the argument sequence indicating the position of the last functional Bus Terminal before the error. This signifies a physical break in the K-bus segment occurring after Bus Terminal 'n'.

Häufige Ursachen

  • Break in K-bus communication behind bus terminal n.
  • Faulty bus terminal n causing communication interruption.
  • Loose or damaged cable connection between bus terminals.
  • Intermittent connection issue on the K-bus.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the physical connection of Bus Terminal n+1 (the terminal immediately following the identified position 'n') for proper seating, damage, or wiring issues.

  2. 2

    Replace Bus Terminal n+1 if its physical connection is confirmed as correct and secure, but the error persists.

Alle Codes in diesem Handbuch durchsuchen (19)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Beckhoff CX2100-0914 Embedded PC