F2033
External power supply X10 error
Bosch Rexroth · IndraDrive C Drive Controllers
Was bedeutet F2033 ?
An error has occurred with the external 24VDC power supply connected to terminal X10 of the drive, which typically provides control power to the drive or external I/O.
Häufige Ursachen
- Loss of 24VDC supply voltage at terminal X10.
- Overload or short circuit on the 24VDC supply circuit connected to X10.
- Faulty external 24VDC power supply unit.
- Loose or incorrect wiring to terminal X10.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure the 24VDC supply voltage at terminal X10 and ensure it is present and stable.
- 2
Check for any short circuits or overloads on the 24VDC circuit connected to X10. Disconnect loads to isolate the problem.
- 3
Inspect the wiring to terminal X10 for loose connections, damage, or incorrect polarity.
- 4
Verify the external 24VDC power supply unit is functioning correctly and delivering the rated current.