Übersetzen...
F2833

Ground fault in motor line

Bosch Rexroth · IndraDrive MPx02

Was bedeutet F2833 ?

A ground fault has been detected in the motor wiring or the motor itself. This means that current is flowing from one of the motor phases to ground, bypassing the normal current path. A ground fault is a serious safety concern and can cause damage to the drive's output stage or the motor insulation.

Häufige Ursachen

  • Damaged motor cable insulation
  • Moisture or contamination in the motor terminal box or motor winding
  • Motor winding insulation breakdown
  • Loose or incorrect grounding connections
  • Damaged cable conduit allowing contact with grounded surfaces

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect the motor power cable routing, external jacket integrity, and connections at both the IndraDrive MPx02 output terminals and the motor terminal box for visible damage, loose connections, moisture ingress, or signs of arcing.

  2. 2

    Disconnect the motor power cable from the IndraDrive MPx02 output terminals (U, V, W, PE) to electrically isolate the motor and the motor cable from the drive.

  3. 3

    Measure the insulation resistance between each individual phase conductor (U, V, W) of the disconnected motor cable and protective earth (PE) using a megohmmeter (e.g., 500 VDC test voltage). Verify readings meet or exceed manufacturer specifications.

  4. 4

    Measure the insulation resistance between each motor winding phase (U, V, W) and the motor frame/protective earth (PE) directly at the motor terminal box to identify any internal motor winding ground fault. Verify readings meet or exceed manufacturer specifications.

Alle Codes in diesem Handbuch durchsuchen (99)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes