F2860

Overcurrent in mains-side power section

Bosch Rexroth · IndraDrive Troubleshooting

Was bedeutet F2860 ?

The current in the power transistor bridge has exceeded the maximum allowed device peak current. This results in the immediate de-energization of the drive, causing the motor to coast to a stop. The power supply is switched off due to this excessive current condition.

Häufige Ursachen

  • Short circuit in motor or motor cable.
  • Device defective.
  • Current loop parameterized differently (not for HMV01.1R), i.e., parameters do not match motor datasheet.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check motor cable and motor for short circuits.

  2. 2

    Replace the device.

  3. 3

    Check current loop parameters to see whether they differ from the parameters on the motor data sheet; correct them if necessary.