Übersetzen...
2821

Serial port overflow

Danfoss · VLT AutomationDrive FC 301/302

Was bedeutet 2821 ?

The serial port buffer has overflowed, indicating that data is being received faster than it can be processed. This can lead to loss of communication or corrupted data.

Häufige Ursachen

  • Data being transmitted to the serial port (e.g., RS-485, RS-232) at a baud rate higher than the drive's processing capability.
  • Excessive, unsolicited communication messages from a connected master device.
  • Software bug in the drive's serial communication handler failing to process incoming data quickly enough.
  • High processor load within the drive diverting resources from serial communication tasks.
  • Intermittent noise on the serial lines corrupting data and causing re-transmission attempts that fill the buffer.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Reduce the baud rate of the connected master device to match P8-10 (Baud rate) or a lower, more stable rate.

  2. 2

    Verify Parameter P8-11 (Protocol) is correctly configured for the connected device (e.g., FC Protocol, Modbus RTU).

  3. 3

    Check the integrity of the serial communication cable for proper shielding and verify termination resistors are correctly installed.

  4. 4

    Monitor the communication traffic using a protocol analyzer to identify if an external device is sending excessive data.

  5. 5

    Update the drive firmware to the latest available version to address potential communication handler bugs.

Alle Codes in diesem Handbuch durchsuchen (66)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Danfoss VLT AutomationDrive FC 301/302