Serial port overflow
Danfoss · VLT AutomationDrive FC 301/302
Was bedeutet 2821 ?
The serial port buffer has overflowed, indicating that data is being received faster than it can be processed. This can lead to loss of communication or corrupted data.
Häufige Ursachen
- Data being transmitted to the serial port (e.g., RS-485, RS-232) at a baud rate higher than the drive's processing capability.
- Excessive, unsolicited communication messages from a connected master device.
- Software bug in the drive's serial communication handler failing to process incoming data quickly enough.
- High processor load within the drive diverting resources from serial communication tasks.
- Intermittent noise on the serial lines corrupting data and causing re-transmission attempts that fill the buffer.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Reduce the baud rate of the connected master device to match P8-10 (Baud rate) or a lower, more stable rate.
- 2
Verify Parameter P8-11 (Protocol) is correctly configured for the connected device (e.g., FC Protocol, Modbus RTU).
- 3
Check the integrity of the serial communication cable for proper shielding and verify termination resistors are correctly installed.
- 4
Monitor the communication traffic using a protocol analyzer to identify if an external device is sending excessive data.
- 5
Update the drive firmware to the latest available version to address potential communication handler bugs.