DC link voltage low
Danfoss · VLT AutomationDrive FC 301/302
Was bedeutet 6 ?
The DC-link voltage is lower than the drive's low-voltage warning limit, which depends on the drive voltage rating. The unit remains active at this warning state, but a further drop could lead to an undervoltage trip.
Häufige Ursachen
- Low incoming mains voltage falling below the drive's nominal operating range (e.g., 360V instead of 400V).
- Transient voltage sag on the mains supply during heavy load starting or switching events upstream.
- Loose connection or high resistance in the incoming mains power circuit or input choke connections.
- Internal power supply issue within the drive causing incorrect DC-link voltage measurement.
- Heavy motor load causing excessive current draw and a subsequent voltage drop across internal components.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure the incoming AC line-to-line voltage at the drive's input terminals (e.g., L1-L2, L2-L3, L3-L1) and confirm stability under load.
- 2
Monitor the DC-link voltage (e.g., via LCP or terminals +DC, -DC) during normal operation and load transients.
- 3
Inspect all connections of the incoming mains power cables at the drive's input terminals (e.g., X1) for tightness and corrosion.
- 4
Check for significant voltage drops across upstream contactors, fuses, or circuit breakers under full motor load.
- 5
Verify parameter P1-54 (Motor Rated Voltage) is set correctly for the application's actual motor and supply voltage.