ALARM 38

Internal fault

Danfoss · VLT HVAC Basic FC 101

Was bedeutet ALARM 38 ?

An unspecified internal fault has occurred within the frequency converter. This indicates a potential hardware or firmware issue requiring specialized attention, and continued operation may cause further damage.

Häufige Ursachen

  • Transient voltage spike or electromagnetic interference (EMI) disrupting internal drive logic.
  • Corruption of firmware or internal configuration settings.
  • Hardware failure on the control card or power card (e.g., processor, memory).
  • Internal communication bus error between drive modules (e.g., control card to power card).
  • Overheating of internal components not detected by specific thermal sensors.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Perform a full power cycle of the drive (disconnect input power for at least 60 seconds) to reset all internal electronics.

  2. 2

    Record the exact fault code and any associated diagnostic or sub-code information displayed on the LCP (e.g., from P15-02 Fault Log).

  3. 3

    Check the drive's environment for excessive heat, dust, or potential sources of strong electromagnetic interference (e.g., arc welders).

  4. 4

    Perform a factory reset of drive parameters (e.g., P14-22 or P14-23) and carefully re-enter essential motor and application parameters.

  5. 5

    If the fault persists, replacement of the control card or the entire drive unit may be necessary after consulting the manufacturer's diagnostic guides.