ALARM 3

No motor

Danfoss · VLT HVAC Drive High Power

Was bedeutet ALARM 3 ?

No motor is connected to the output of the frequency converter. This prevents motor operation and could indicate a wiring issue or incorrect system setup.

Häufige Ursachen

  • Motor not physically connected to the frequency converter's output terminals (U, V, W).
  • Broken motor cable or loose connections between the frequency converter and the motor terminal box.
  • Incorrect motor parameter settings, such as P1-03 (Motor kW) or P1-04 (Motor V), preventing motor recognition.
  • Internal open circuit within the motor windings (e.g., one phase disconnected), preventing the frequency converter from detecting a load.
  • Faulty current measurement circuit within the frequency converter itself.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Visually inspect the motor cable connections at both the frequency converter output (U, V, W) and the motor terminal box.

  2. 2

    Measure the resistance between the U, V, W output terminals of the frequency converter (with power off) to confirm motor winding continuity.

  3. 3

    Verify motor nameplate data against frequency converter parameters P1-03 (Motor kW), P1-04 (Motor V), P1-05 (Motor A), P1-06 (Motor cos phi), P1-07 (Motor Speed).

  4. 4

    Check for an open circuit within the motor windings by measuring resistance directly at the motor terminal box.

  5. 5

    Perform an Automatic Motor Adaptation (AMA) via parameter P8-10 (Auto Adapt) to allow the frequency converter to characterize the connected motor.