Mains failure
Danfoss · VLT HVAC Drive High Power
Was bedeutet ALARM 36 ?
The supply voltage to the frequency converter is lost. This warning/alarm is active only if parameter 14-10 Mains Failure is not set to [0] No Function. This causes a complete loss of power to the drive and connected motor.
Häufige Ursachen
- Complete loss of incoming three-phase (or single-phase) AC supply voltage to the frequency converter input terminals.
- Tripped upstream circuit breaker, blown fuse, or open motor protection switch in the main power circuit.
- Loose or corroded connections in the input power path (e.g., main contactor, input reactor, terminal blocks).
- Significant and prolonged voltage sag below the frequency converter's undervoltage trip threshold (e.g., below 340V AC for 400V drive).
- Faulty internal voltage sensing circuit in the frequency converter, incorrectly detecting a mains failure.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Measure the incoming AC line voltage (L1, L2, L3) at the frequency converter input terminals (e.g., R, S, T) using a multimeter.
- 2
2. Inspect and reset any tripped upstream circuit breakers, blown fuses, or motor protection switches in the input power circuit.
- 3
3. Check the tightness of all input power wiring connections at the frequency converter and any upstream isolation devices.
- 4
4. Review parameter P14-10 Mains Failure setting to ensure it's configured for the desired response to power loss (e.g., [0] No Function).
- 5
5. Monitor the AC supply voltage with a power quality analyzer to detect intermittent power loss events or severe sags.