Übersetzen...
30

Motor phase U missing

Danfoss · VLT Micro Drive FC 51

Was bedeutet 30 ?

One of the motor output phases (Phase U) is detected as missing by the drive. This usually points to a disconnected motor cable, a broken wire, or a poor connection at either the drive or motor terminals, preventing proper motor operation.

Häufige Ursachen

  • Open circuit in the motor cable for phase U between the drive's U terminal and the motor's U terminal.
  • Loose or corroded connection at the drive's output terminal U or the motor's terminal box for phase U.
  • Internal failure of an output IGBT (Insulated Gate Bipolar Transistor) for phase U within the drive.
  • Open circuit fault in the motor winding for phase U, resulting in no current path.
  • Dislodged or damaged busbar connection for phase U inside the drive's power section.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    De-energize the drive and verify 0VDC at the drive's U, V, W output terminals.

  2. 2

    Measure continuity of the motor cable for phase U from the drive's U terminal to the motor's U terminal.

  3. 3

    Inspect connections at drive terminal U and the motor's terminal box for phase U for looseness, corrosion, or damage.

  4. 4

    Measure resistance of the motor windings (U-V, V-W, W-U) at the motor's terminal box, verifying they are balanced and within specification (e.g., 0.5-20 Ohms).

  5. 5

    If motor and cable are confirmed good, measure resistance between drive output terminal U and the DC bus (+) and (-) terminals to check for IGBT integrity.

Alle Codes in diesem Handbuch durchsuchen (51)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes