Übersetzen...
SRVO-231

Safety Chain 2 Abnormal

Fanuc · R-30iB Mate + Mate Plus Robot

Was bedeutet SRVO-231 ?

A mismatch has occurred between duplicate safety signals. Specifically, a contact on the chain 1 side (e.g., between EES1 and EES11, or EAS1 and EAS11) is open, while the corresponding contact on the chain 2 side (e.g., between EES2 and EES21, or EAS2 and EAS21) is closed. This condition indicates a potential failure or discrepancy in one of the redundant safety circuits, compromising safety integrity.

Häufige Ursachen

  • Safety Chain 2 has detected an abnormal condition, interrupting normal operation.
  • Similar to Safety Chain 1, this fault is related to the second safety interlock circuit, indicating an issue with its components or wiring.
  • The control system has halted operation due to a fault in the secondary safety monitoring system.
  • Inspect all components and wiring connected to Safety Chain 2 for faults.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check any other SRVO-266 through SRVO-275 and SRVO-370 through SRVO-385 alarms issued simultaneously to identify the specific signal with the mismatch.

  2. 2

    Take corrective action(s) as described for any concurrently issued alarms.

  3. 3

    Do not reset the chain error alarm until the failure is identified and repaired to ensure safety.

  4. 4

    After correcting the cause of the alarm, perform the chain error reset procedure as described in the manual.

Alle Codes in diesem Handbuch durchsuchen (53)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Fanuc R-30iB Mate + Mate Plus Robot