Übersetzen...
448
Neutral conductor not connected
Fronius · Primo GEN24 Operating Instructions
Was bedeutet 448 ?
This code indicates that the neutral conductor is not correctly connected. For certain grid configurations, a missing neutral connection is critical for proper operation and safety, preventing the inverter from feeding energy into the grid.
Häufige Ursachen
- Loose or disconnected neutral wire in the AC grid connection.
- Incorrect wiring during inverter installation.
- Faulty neutral connection point within the inverter or switchgear.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
If the status code is displayed continuously, notify a Fronius-trained service engineer for wiring inspection.
- 2
Verify the integrity and connection of the neutral conductor at the inverter's AC terminals and grid connection point.
- 3
Measure the AC voltage between phases and neutral to confirm proper connection.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Fronius Primo GEN24 Operating Instructions