Übersetzen...
1030

WSD Open

Fronius · Symo Advanced

Was bedeutet 1030 ?

This status indicates that a device connected in the Wired Shutdown (WSD) chain has interrupted the signal line, possibly due to a tripped surge protection device (SPD), the removal of an installed bypass, or a missing trigger device. This condition results in the inverter's operating LED flashing red. It prevents normal operation until the WSD chain integrity is restored.

Häufige Ursachen

  • A device in the WSD chain, such as a surge protection device, has interrupted the signal line.
  • The bypass installed ex works as standard has been removed from the WSD chain.
  • A required trigger device has not been installed in the WSD chain.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    If an SPD surge protection device has tripped, arrange for the inverter to be repaired by an authorized specialist.

  2. 2

    Install the bypass installed ex works as standard or a suitable trigger device into the WSD chain.

  3. 3

    Turn the WSD (wired shutdown) switch to position 1 (WSD primary device) to enable the primary device functionality.

Alle Codes in diesem Handbuch durchsuchen (41)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes