2062

Low insulation resistance

Huawei · SUN2000-(3KTL-10KTL)-M1 Solar Inverter

Was bedeutet 2062 ?

A short circuit exists between the PV array and the ground, or the PV array is in a moist environment with poor insulation. This is a critical safety fault indicating potential electrical leakage.

Häufige Ursachen

  • A short circuit exists between the PV array and the ground.
  • The PV array is in a moist environment and the circuit is not well insulated to the ground.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the impedance between the PV array output and the ground. If a short circuit occurs or the insulation is insufficient, rectify the fault.

  2. 2

    Check whether the PE cable of the SUN2000 is correctly connected.

  3. 3

    If the impedance is confirmed to be lower than the specified protection threshold in a cloudy or rainy environment, log in to the app, SmartLogger, or NMS and set the Insulation resistance protection threshold.