2061
Abnormal Grounding
Huawei · SUN2000 Solar Inverter
Was bedeutet 2061 ?
The N (Neutral) cable or ground cable is not properly connected, or if a PV array is grounded, the inverter output is not connected to an isolation transformer. This indicates a potential safety hazard due to incorrect grounding.
Häufige Ursachen
- The N cable is not connected.
- The ground cable is not connected.
- When a PV array is grounded, the inverter output is not connected to an isolation transformer.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Power off the inverter.
- 2
Check whether the PE cable of the SUN2000 is connected properly.
- 3
If the inverter is connected to the TN power grid, check whether the N cable is properly connected and whether the voltage of the N cable to ground is normal.
- 4
Check whether the output is connected to an isolation transformer. If yes, set 'Grounding inspection' to 'Disable' through the mobile phone app, SmartLogger, or NMS.