Übersetzen...
E353

Diagnostic message power supply erroneous

Indramat · CLM01.3-M Flying Cutoff Control

Was bedeutet E353 ?

The Indramat HVE or HVR power supply unit cyclically sends status and error messages via a serial connection to the connected controller (DIAX04 SSE-03VRS). This warning is generated if the controller does not receive several sequential messages, indicating a communication breakdown.

Häufige Ursachen

  • The serial interface of the power supply unit (HVE/HVR) is defective.
  • A break or damage in the serial connection lines (bus cable) between the power supply unit and the controller.
  • The serial interface of the controller (DIAX04 SSE-03VRS) is defective.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Visually inspect the serial bus cable connecting the HVE/HVR power supply unit to the DIAX04 SSE-03VRS controller for any signs of damage or loose connections.

  2. 2

    Check the termination and continuity of the bus cable, and replace it if necessary.

  3. 3

    If the bus cable and connections are verified, consider replacing the HVE/HVR power supply unit if its serial interface is suspected to be defective.

  4. 4

    If the fault persists after checking the cable and power supply, the serial interface of the DIAX04 SSE-03VRS controller may be defective, requiring controller replacement.

Alle Codes in diesem Handbuch durchsuchen (31)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Indramat CLM01.3-M Flying Cutoff Control