Übersetzen...
F381

Mains failure

Indramat · CLM01.3-M Flying Cutoff Control

Was bedeutet F381 ?

With HVR power supply units only! At least one phase of the 3-phase power supply input to the HVR unit is missing, indicating a loss of input power.

Häufige Ursachen

  • At least one phase of the 3-phase power supply input to the HVR unit is missing.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the incoming 3-phase power supply at the input terminals of the Indramat HVR power supply unit (X1/L1, X1/L2, X1/L3) using a multimeter. Confirm all three phases are present and balanced.

  2. 2

    Inspect all upstream mains fuses and circuit breakers for the power supply unit. Replace any blown fuses or reset tripped breakers.

  3. 3

    Check power contactors and their auxiliary contacts for proper operation and engagement in the power distribution circuit.

  4. 4

    Inspect all power wiring connections from the mains supply to the HVR unit for looseness, damage, or disconnections.

Alle Codes in diesem Handbuch durchsuchen (31)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Indramat CLM01.3-M Flying Cutoff Control