F385

Line frequency fault

Indramat · CLM01.3-M Flying Cutoff Control

Was bedeutet F385 ?

With HVR power supply units only! The mains frequency exceeds the permissible tolerance of ± 2Hz, indicating a deviation from the expected 50Hz or 60Hz nominal frequency.

Häufige Ursachen

  • Mains frequency exceeds permissible tolerance (± 2Hz) from the nominal system frequency.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the incoming line frequency at the input terminals of the Indramat HVR power supply unit (X1/L1, X1/L2, X1/L3) using a frequency meter or a multimeter with frequency measurement capability.

  2. 2

    Verify the measured frequency is consistently within ±2Hz of the nominal system frequency (e.g., 50Hz ± 2Hz or 60Hz ± 2Hz).

  3. 3

    Check the stability of the upstream power grid and the power source quality.

  4. 4

    If available, review power quality logs or consult with the power utility provider regarding frequency variations or instability.