Excessive Deviation
Indramat · ECODRIVE Controller
Was bedeutet F228 ?
The drive was unable to process the given command value, resulting in a deviation from the commanded position/velocity that exceeded an allowable limit. The drive reacted by shutting down according to the set error reaction to prevent mechanical damage or uncontrolled movement.
Häufige Ursachen
- The acceleration ability of the drive was exceeded.
- The motor shaft was blocked.
- Parameterization error in the drive parameters (control loop settings).
- S-0-0159, Monitoring Window, was parameterized incorrectly.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the Bipolar Torque Limit, parameter S-0-0092, and ensure it is set to the maximum allowable value for the application and motor.
- 2
Inspect the mechanical system for any binding, jamming, or blockage of the motor shaft or connected load, and eliminate the obstruction.
- 3
Review all relevant drive control loop parameters (e.g., gains, filters) to ensure they are correctly tuned for the application and motor.
- 4
Verify and correctly parameterize S-0-0159, Monitoring Window, to an appropriate value for the application's tolerance for deviation.
- 5
Reduce commanded acceleration or deceleration rates to remain within the drive's and mechanical system's capabilities.