Velocity command value limit activ
Indramat · IndraDrive MPx02
Was bedeutet E2059 ?
The current velocity command value for the IndraDrive MPx02 is being limited by a configured maximum velocity parameter. This is a warning indicating that the requested velocity exceeds the allowed limit, and the drive is automatically capping it to prevent overspeed or mechanical stress.
Häufige Ursachen
- The commanded velocity from the master controller exceeds the maximum allowed velocity set in a drive parameter (e.g., P-0-0090, Velocity command value limit).
- Incorrect application scaling or unit conversion for the velocity command.
- A safety-related velocity limit is active, overriding the standard operating limits.
- The velocity limit parameter is set too conservatively for the intended operation.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the current value of the velocity limit parameter (e.g., P-0-0090) in the IndraDrive MPx02 and compare it to the commanded velocity from the master controller.
- 2
Adjust the commanded velocity from the master controller to be within the allowed range of the IndraDrive MPx02 and the application's mechanical limits.
- 3
If a higher velocity is legitimately required, review and increase the velocity limit parameter in the drive configuration, ensuring it remains within the motor and mechanical system capabilities.
- 4
Check for any active safety functions or system interlocks that might be imposing additional velocity limitations.