Undervoltage in power section
Indramat · IndraDrive MPx02
Was bedeutet E8026 ?
This warning signifies that the DC bus voltage within the IndraDrive MPx02's power section has dropped below a specified undervoltage threshold. This can lead to reduced motor performance and, if prolonged, can trigger a fault condition to protect the drive from improper operation.
Häufige Ursachen
- Insufficient incoming AC mains voltage to the drive.
- Excessive load current demand causing transient DC bus voltage sag.
- High resistance connections in the power supply path (e.g., loose wires, faulty contactors).
- Internal DC bus capacitor degradation, reducing its energy storage capacity.
- Temporary power dip in the mains supply.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure the incoming AC mains voltage at the drive input terminals (L1, L2, L3) and confirm it is stable and within the drive's specified operating range.
- 2
Monitor the actual DC bus voltage through the IndraDrive MPx02's diagnostic interface during operation, especially under peak load conditions.
- 3
Inspect all power cable connections, circuit breakers, and contactors in the power supply circuit for tightness and absence of corrosion or damage.
- 4
Reduce the dynamic load on the motor or optimize the motion profile to prevent sudden, large current demands that could cause DC bus sag.
- 5
Verify that the drive's nominal mains voltage parameter (e.g., P-0-0120) is correctly set to match the actual supply voltage.