F8813

Connection error mains choke

Indramat · Indradrive

Was bedeutet F8813 ?

The IndraDrive detected an issue with the connection or functionality of the external mains choke. The mains choke is used for suppressing harmonics and limiting inrush current, and a connection error can lead to power quality issues or prevent safe operation.

Häufige Ursachen

  • Loose or incorrect wiring of the mains choke.
  • Damaged or faulty mains choke unit.
  • Open circuit in one or more phases of the choke connection.
  • Incorrectly sized or incompatible mains choke.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Disconnect input power and visually inspect the wiring connections between the mains supply, the mains choke, and the IndraDrive input terminals for tightness and correct phasing.

  2. 2

    Perform continuity tests on the mains choke windings to check for open circuits or damage.

  3. 3

    Verify that the mains choke is correctly sized and specified for the IndraDrive and supply voltage.

  4. 4

    Ensure proper grounding of the mains choke and associated cabling.

  5. 5

    If the choke itself is suspected to be faulty after inspection, consider replacing it.