Overvoltage

Kone · CMXC-022 Frequency Control Upgrade Kit

Was bedeutet 2 ?

The R&M Materials Handling Frequency Converter has detected an overvoltage condition, which could be caused by an excessively high supply voltage or a fault in the braking resistor circuit. Issues such as a failure of the resistor itself or a break in its wiring can trigger this fault.

Häufige Ursachen

  • Supply voltage exceeding the rated input range
  • Failure of the braking resistor
  • Break in the braking resistor wiring

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the supply voltage and compare it to the specified hoist supply voltage on the hoist type plate

  2. 2

    Measure the resistance of the braking resistor

  3. 3

    Perform a visual inspection of the braking resistor and its wiring connections