Übersetzen...
1075

CONTACTOR DRIVER

Kone · Elevator Control

Was bedeutet 1075 ?

The motor controller (codes 1075, 2075, 3075) has detected a fault in the main contactor driver circuit. This affects the ability to control the main power contactor. The specific lift reaction is controller dependent.

Häufige Ursachen

  • Contactor driver circuit open or shorted.
  • Contactor coil fault (e.g., open circuit, short circuit).
  • Internal controller hardware failure affecting the driver output.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the auxiliary control voltage supply to the motor controller's contactor driver circuit.

  2. 2

    Inspect wiring and connections between the motor controller's contactor driver output and the main power contactor coil for damage, corrosion, or loose terminals.

  3. 3

    Measure the resistance of the main power contactor coil to confirm it is within the manufacturer's specified range (check for open or short circuit).

  4. 4

    Measure the voltage at the main power contactor coil terminals during a commanded activation attempt to verify the driver's output signal.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes