Übersetzen...
Overvoltage PMx
KPS Intermediate Circuit Overvoltage During Operation
Kuka · KR C2 Robot Controller
Was bedeutet Overvoltage PMx ?
An overvoltage condition has been detected in the intermediate circuit of the KPS module (PMx) during operation. This can be caused by excessively high mains voltage or a defective ballast switch not dissipating regenerative energy.
Häufige Ursachen
- Intermediate circuit voltage exceeds the safe limit during operation.
- Regenerative braking feedback too high without sufficient load.
- Power supply fluctuations.
- Faulty capacitor bank in the intermediate circuit.
- Overvoltage protection device failure.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure the incoming mains voltage at the KPS input terminals. If it exceeds specifications, identify and rectify the source of the high voltage.
- 2
If the mains voltage is within specifications, the ballast switch inside the KPS module may be defective; exchange the KPS module.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Kuka KR C2 Robot Controller